Signal
Description
IDIFF
Magnitude of fundamental frequency differential current
ANGLE
Direction angle from zero sequence feature
I2RATIO
Second harmonic ratio
6.2.5
Settings
Table 38:
Basic general settings for the function REFPDIF (REF1-)
Parameter
Range
Step
Default
Unit
Description
GlobalBaseSel
1 - 6
1
1
-
Selection of one of
the Global Base
Value groups
Table 39:
Basic parameter group settings for the function REFPDIF (REF1-)
Parameter
Range
Step
Default
Unit
Description
Operation
Off
On
-
Off
-
Operation Off / On
IdMin
4.0 - 100.0
0.1
10.0
%IB
Maximum sensitivity
in % of IBase
Table 40:
Advanced parameter group settings for the function REFPDIF (REF1-)
Parameter
Range
Step
Default
Unit
Description
ROA
60 - 90
1
60
Deg
Relay operate angle
for zero sequence
directional feature
6.2.6
Monitored data
Table 41:
REFPDIF Monitored data
Name
Type
Values (Range)
Unit
Description
IRES
REAL
-
A
Magnitude of
fundamental frequency
residual current
IN
REAL
-
A
Magnitude of
fundamental frequency
neutral current
IBIAS
REAL
-
A
Magnitude of the bias
current
IDIFF
REAL
-
A
Magnitude of
fundamental frequency
differential current
ANGLE
REAL
-
deg
Direction angle from zero
sequence feature
I2RATIO
REAL
-
-
Second harmonic ratio
Section 6
1MRK 504 135-UEN A
Differential protection
112
Technical manual
Содержание ret650
Страница 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Страница 2: ......
Страница 40: ...34 ...
Страница 62: ...56 ...
Страница 84: ...78 ...
Страница 208: ...202 ...
Страница 353: ...Table 236 Gray code conversion IEC06000523 V1 EN 1MRK 504 135 UEN A Section 12 Control 347 Technical manual ...
Страница 376: ...370 ...
Страница 414: ...408 ...
Страница 530: ...524 ...
Страница 562: ...556 ...
Страница 620: ...614 ...
Страница 668: ...662 ...
Страница 669: ...663 ...