in false differential currents - consisting exclusively of the zero sequence currents. If
high enough, these false differential currents can cause an unwanted disconnection of
the healthy power transformer. They must therefore be subtracted from the
fundamental frequency differential currents if an unwanted trip is to be avoided.
For delta windings this feature shall be enabled only if an earthing transformer exist
within the differential zone on the delta side of the protected power transformer.
Removing the zero sequence current from the differential currents decreases to some
extent the sensitivity of the differential protection for internal earth-faults. In order to
counteract this effect to some degree, the zero sequence current is subtracted not only
from the three fundamental frequency differential currents, but from the bias current
as well.
6.1.4.6
Restrained and unrestrained limits of the differential protection
The power transformer differential protection function uses two limits, to which
actual magnitudes of the three fundamental frequency differential currents are
compared at each execution of the function.
The unrestrained (that is, non-stabilized, "instantaneous") part of the differential
protection is used for very high differential currents, where it should be beyond any
doubt, that the fault is internal. This settable limit is constant and not proportional to
the bias current. Neither harmonic, nor any other restrain is applied to this limit, which
is therefore capable to trip the power transformer instantaneously.
The restrained (stabilized) part of the differential protection compares the calculated
fundamental differential (operating) currents and the bias (restrain) current, by
applying them to the operate - restrain characteristic. The operate - restrain
characteristic is represented by a double-slope, double-breakpoint diagram, where the
operating current is set against the bias current, as shown in figure
characteristic is determined by the following 5 settings:
1.
IdMin
(Sensitivity in section 1, multiple of trans. Reference side rated current set
under the parameter
IBase in GlobalbaseSelW1
)
2.
EndSection1
(End of section 1, as multiple of transformer reference side rated
current set under the parameter
IBase in GlobalbaseSelW1
)
3.
EndSection2
(End of section 2, as multiple of transformer reference side rated
current set under the parameter
IBase in GlobalbaseSelW1
)
4.
SlopeSection2
(Slope in section 2, as multiple of transformer reference side rated
current set under the parameter
IBase in GlobalbaseSelW1
)
5.
SlopeSection3
(Slope in section 2, as multiple of transformer reference side rated
current set under the parameter
IBase in GlobalbaseSelW1
)
Section 6
1MRK 504 135-UEN A
Differential protection
94
Technical manual
Содержание ret650
Страница 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Страница 2: ......
Страница 40: ...34 ...
Страница 62: ...56 ...
Страница 84: ...78 ...
Страница 208: ...202 ...
Страница 353: ...Table 236 Gray code conversion IEC06000523 V1 EN 1MRK 504 135 UEN A Section 12 Control 347 Technical manual ...
Страница 376: ...370 ...
Страница 414: ...408 ...
Страница 530: ...524 ...
Страница 562: ...556 ...
Страница 620: ...614 ...
Страница 668: ...662 ...
Страница 669: ...663 ...