1MAC309294-MB F
Section 7
Measurement functions
RER620
383
Technical Manual
Section 7
Measurement functions
7.1
Basic measurements
7.1.1
Functions
The three-phase current measurement function, IA, IB, IC, is used for monitoring and
metering the phase currents of the power system.
The three-phase voltage measurement function, VA, VB, VC, is used for monitoring and
metering the phase-to-phase voltages of the power system. The phase-to-ground voltages
are also available in VA, VB, VC.
The ground current measurement function, IG, is used for monitoring and metering the
ground current of the power system.
The ground voltage measurement function, VG, is used for monitoring and metering the
ground voltage of the power system.
The sequence current measurement, I1, I2, I0, is used for monitoring and metering the
phase sequence currents.
The sequence voltage measurement, V1, V2, V0, is used for monitoring and metering the
phase sequence voltages.
The three-phase power and energy measurement P,SP, E is used for monitoring and
metering the active power P, reactive power Q, apparent power S, power factor PF on
individual phases as well as three phase total and for calculating the accumulated energy
separately on three phase total basis as forward active, reverse active, forward reactive and
reverse reactive. P, SP, E calculates these quantities with the fundamental frequency
phasors, that is, the DFT values of the measured phase current and phase voltage signals.
The information of the measured quantity is available for the operator both locally in
LHMI and remotely to a network control center with communication.
7.1.2
Measurement functionality
The functions can be enabled or disabled with the
Operation
setting. The corresponding
parameter values are Enable and Disable.
Some of the measurement functions operate on two alternative measurement modes:
“DFT” and “RMS”. The measurement mode is selected with the
X Measurement mode
setting. Depending on the measuring function if the measurement mode cannot be
selected, the measuring mode is “DFT”.
Содержание RER620
Страница 1: ...Relion Protection and Control Advanced Recloser Protection and Control RER620 Technical Manual ...
Страница 2: ......
Страница 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Страница 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Страница 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Страница 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Страница 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Страница 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Страница 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Страница 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Страница 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Страница 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Страница 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Страница 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Страница 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Страница 583: ......