1MAC309294-MB F
Section 4
Protection functions
RER620
207
Technical Manual
4.3.3.4
Operation principle
The function can be enabled and disabled with the
Operation
setting. The corresponding
parameter values are Enable and Disable.
The operation of residual overvoltage protection can be described by using a module
diagram. All the blocks in the diagram are explained in the next sections.
Figure 94:
Functional module diagram. V
N
represents the zero sequence voltage.
Level detector
The measured or calculated zero sequence voltage is compared with the set
Pickup value
.
If the value exceeds the set
Pickup value
, the level detector sends an enable-signal to the
timer.
Timer
Once activated, the timer activates the
PICKUP
output. The time characteristic is
according to DT. When the trip timer has reached the value set by
Trip delay time
, the
TRIP
output is activated. If the fault disappears before the module trips, the reset timer is
activated. If the reset timer reaches the value set by
Reset delay time
, the trip timer resets
and the
PICKUP
output is deactivated.
The timer calculates the pickup duration (PICKUP_DUR) value which indicates the ratio
of the pickup situation and the set trip time. The value is available through the Monitored
data view.
Blocking logic
There are three operation modes in the blocking functionality. The operation modes are
controlled by the
BLOCK
input and the global setting “
Configuration/System/
Blocking
mode”
which selects the blocking mode. The
BLOCK
input can be controlled by a binary
input, a horizontal communication input or an internal signal of the relay program. The
influence of the
BLOCK
signal activation is preselected with the global setting
Blocking
mode
.
The
Blocking mode
setting has three blocking methods. In the “Freeze timers” mode, the
trip timer is frozen to the prevailing value. In the “Block all” mode, the whole function is
V
N
BLOCK
Level
detector
TRIP
PICKUP
Blocking
logic
t
Timer
Содержание RER620
Страница 1: ...Relion Protection and Control Advanced Recloser Protection and Control RER620 Technical Manual ...
Страница 2: ......
Страница 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Страница 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Страница 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Страница 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Страница 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Страница 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Страница 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Страница 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Страница 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Страница 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Страница 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Страница 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Страница 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Страница 583: ......