Section 4
1MAC309294-MB F
Protection functions
194
RER620
Technical Manual
Blocking logic
There are three operation modes in the blocking functionality. The operation modes are
controlled by the
BLOCK
input and the global setting
Configuration > System > Blocking
mode
which selects the blocking mode. The
BLOCK
input can be controlled by a binary
input, a horizontal communication input or an internal signal of the relay program. The
influence of the
BLOCK
input signal activation is preselected with the global
Blocking
mode
setting.
The
Blocking mode
setting has three blocking methods. In the “Freeze timers” mode, the
operate timer is frozen to the prevailing value. In the “Block all” mode, the whole function
is blocked and the timers are reset. In the “Block OPERATE output” mode, the function
operates normally but the
OPERATE
output is not activated.
4.3.1.5
Timer characteristics
The operating curve types supported by 59 are:
Table 202: Timer characteristics supported by IDMT operate curve types
4.3.1.6
Application
Overvoltage in a network occurs either due to the transient surges on the network or due
to prolonged power frequency overvoltages. Surge arresters are used to protect the
network against the transient overvoltages, but the relay protection function is used to
protect against power frequency overvoltages.
The power frequency overvoltage may occur in the network due to the contingencies such
as:
• The defective operation of the automatic voltage regulator when the generator is in
isolated operation.
• Operation under manual control with the voltage regulator out of service. A sudden
variation of load, in particular the reactive power component, gives rise to a
substantial change in voltage because of the inherent large voltage regulation of a
typical alternator.
• Sudden loss of load due to the tripping of outgoing feeders, leaving the generator
isolated or feeding a very small load. This causes a sudden rise in the terminal voltage
due to the trapped field flux and overspeed.
The “Freeze timers” mode of blocking has no effect during the “Inverse
reset” mode.
Operating curve type
(5) ANSI Def. Time
(15) IEC Def. Time
(17) Inv. Curve A
(18) Inv. Curve B
(19) Inv. Curve C
(20) Programmable
Содержание RER620
Страница 1: ...Relion Protection and Control Advanced Recloser Protection and Control RER620 Technical Manual ...
Страница 2: ......
Страница 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Страница 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Страница 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Страница 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Страница 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Страница 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Страница 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Страница 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Страница 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Страница 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Страница 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Страница 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Страница 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Страница 583: ......