structure is used for the control operation. Analog output of RIO600 can be written
only by using the write single register function.
7.1.22
Exception codes
Only a few exception code alternatives exist for the write coil and write register
requests in Modbus. If the write permission has not been provided for the client to
write a value to either binary or analog outputs, RIO600 does not consider the write
request but responds with an exception code for the respective operation.
7.1.23
System status register
SSR1
The device health status SSR1 register is located at 3X/4X address 0. The bits in SSR1
give an overview of the RIO600 health.
Table 119:
System status register 1 (Device health status)
Bit
Value
Description
0
0 = Healthy
1 = Warning or error
LECM warning
1
0 = Healthy
1 = Warning or error
LECM error
2
0 = Healthy
1 = Warning or error
Module 1 health
3
0 = Healthy
1 = Warning or error
Module 2 health
4
0 = Healthy
1 = Warning or error
Module 3 health
5
0 = Healthy
1 = Warning or error
Module 4 health
6
0 = Healthy
1 = Warning or error
Module 5 health
7
0 = Healthy
1 = Warning or error
Module 6 health
8
0 = Healthy
1 = Warning or error
Module 7 health
9
0 = Healthy
1 = Warning or error
Module 8 health
10
0 = Healthy
1 = Warning or error
Module 9 health
11
0 = Healthy
1 = Warning or error
Module 10 health
12
0 = Healthy
1 = UPS power failure
-
13
0 = Remote
1 = Local
-
14
-
-
15
-
-
1MRS757488 H
Section 7
Modbus TCP communication
RIO600
177
Installation and Commissioning Manual
Содержание Remote I/O RIO600
Страница 1: ... Remote I O RIO600 Installation and Commissioning Manual ...
Страница 2: ......
Страница 8: ......
Страница 14: ...6 ...
Страница 18: ...10 ...
Страница 64: ...56 ...
Страница 280: ...272 ...
Страница 306: ...298 ...
Страница 310: ...302 ...
Страница 311: ...303 ...