For Analog Output Module (AOM4), in case of failsafe condition, the module
continues to drive the old value. In case of power-off condition, the module drives 0
mA current.
6.4
Local/Remote mode
RIO600 can be set to Local/Remote mode using any of the binary input signals,
GOOSE signal or through a Modbus command. The Local/Remote mode can be
instantiated using Signal Matrix tool. Different combinations are possible based on
the Local/Remote setting.
Table 113:
Local/Remote mode options
Local/
Remote
mode
OR Logic
Local
Remote
Intermodule
communicati
on support
(commands
from DIM8)
Binary Goose
subscribing
Binary Goose
publishing
Binary
Modbus write
operations
Binary
Modbus read
operations
-
NO
YES
YES
YES
YES
YES
Remote
NO
YES
YES
YES
YES
YES
Local
NO
YES
NO
YES
NO
YES
-
YES
YES
YES
YES
N/A
N/A
Remote
YES
YES
YES
YES
N/A
N/A
Local
YES
YES
NO
YES
N/A
N/A
6.5
Time synchronization
RIO600 can be synchronized to an NTP time server or the time synchronization can
be achieved using Modbus TCP client.
Time synchronization is used to synchronize the device's real time clock. Using time
synchronization, RIO600 can show the correct time in its WHMI and time stamp the
header and data events of GOOSE messages properly.
Time synchronization is not mandatory. The time stamp attribute is
not included by default in GOOSE data sets.
RIO600 does not support DST and therefore the used time is always
UTC in WHMI and events.
Section 6
1MRS757488 H
Commissioning
168
RIO600
Installation and Commissioning Manual
Содержание Remote I/O RIO600
Страница 1: ... Remote I O RIO600 Installation and Commissioning Manual ...
Страница 2: ......
Страница 8: ......
Страница 14: ...6 ...
Страница 18: ...10 ...
Страница 64: ...56 ...
Страница 280: ...272 ...
Страница 306: ...298 ...
Страница 310: ...302 ...
Страница 311: ...303 ...