Figure 86:
Phase-to-phase AB operating conditions (residual current criteria)
Special attention is paid to correct phase selection at evolving faults. A DLECND output
signal is created as a combination of the load encroachment characteristic and current
criteria, refer to figure
. This signal can be configured to PHSEL functional input signals
of the distance protection zone and this way influence the operation of the phase-to-phase
zone measuring elements and their phase related pickup and tripping signals.
7.5.7
Technical data
Table 82:
LEPDIS technical data
Function
Range or value
Accuracy
Load encroachment criteria:
Load resistance, forward and
reverse
Safety load impedance angle
(1.00–3000.00) Ω/phase
(5-85) degrees
± 5.0% static accuracy
± 2.0 degrees static angular
accuracy
Conditions:
Voltage range: (0.1-1.1) x V
n
Current range: (0.5-30) x I
n
Reset ratio
105% typically
-
1MRK 502 048-UUS A
Section 7
Impedance protection
191
Technical manual
Содержание Relion
Страница 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual...
Страница 2: ......
Страница 44: ...38...
Страница 62: ...56...
Страница 68: ...62...
Страница 156: ...150...
Страница 198: ...192...
Страница 512: ...506...
Страница 644: ...638...
Страница 714: ...708...
Страница 777: ...771...