Table 7. Energizing inputs (sensors)
Description
Value
Current sensor input
Rated current voltage (in secondary
side)
75 mV...9000 mV
1)
Continuous voltage withstand
125 V
Input impedance at 50/60 Hz
2...3 MΩ
2)
Voltage sensor input
Rated voltage
6 kV...30 kV
3)
Continuous voltage withstand
50 V
Input impedance at 50/60 Hz
3 MΩ
1)
Equals the current range of 40...4000 A with a 80 A, 3 mV/Hz Rogowski
2)
Depending on the used nominal current (hardware gain)
3)
This range is covered (up to 2*rated) with sensor division ratio of 10 000:1
Table 8. Binary inputs
Description
Value
Operating range
±20% of the rated voltage
Rated voltage
24...250 V DC
Current drain
1.6...1.9 mA
Power consumption
31.0...570.0 mW
Threshold voltage
16...176 V DC
Reaction time
<3 ms
Table 9. Signal output X100: SO1
Description
Value
Rated voltage
250 V AC/DC
Continuous contact carry
5 A
Make and carry for 3.0 s
15 A
Make and carry for 0.5 s
30 A
Breaking capacity when the control-circuit time constant L/R<40 ms, at
48/110/220 V DC
1 A/0.25 A/0.15 A
Minimum contact load
100 mA at 24 V AC/DC
Table 10. Signal outputs and IRF output
Description
Value
Rated voltage
250 V AC/DC
Continuous contact carry
5 A
Make and carry for 3.0 s
10 A
Make and carry 0.5 s
15 A
Breaking capacity when the control-circuit time constant L/R<40 ms, at
48/110/220 V DC
1 A/0.25 A/0.15 A
Minimum contact load
10 mA at 5 V AC/DC
Substation Merging Unit
1MRS758420 B
SMU615
Product version: 1.0