Panel cut-out of 167 × 203 mm with mounting holes
•
Depth behind the panel 107 mm
•
When IP 54 degree of protection (according to IEC 60529) is required for the
front side, a gasket has to be used in the installation.
1.
Mount the angle frame into the panel cut-out with four M4 screws.
B
G
A
H
D
E
F
C
1
3
4
2
GUID-48F6CBAD-92EE-432D-B112-AFBC77EFC3F6 V1 EN
Figure 14:
Mounting the angled frame
A 177 ±0.3 mm
1 Panel
B 167 ±1 mm
2 Angle frame
C 203 ±1 mm
3 Gasket
D 40.5 mm
4 M4 screw
E 122 mm ±0.3 mm
F 40.5 mm
G ∅ 5.5 mm
H 190 mm
2.
Loosen the four M5 fixing screws in the case to fit the case into the angle frame.
3.
Mount the case to the angle frame.
With the angled frame, the merging unit can be mounted inclined downward to
a 25° angle.
4.
Tighten the screws.
Section 4
1MRS758405 C
Mounting
24
SMU615
Installation Manual