![ABB Relion SAM600 Скачать руководство пользователя страница 44](http://html.mh-extra.com/html/abb/relion-sam600/relion-sam600_applications-manual_2830044.webp)
4.11.2
Application
SEMOD158512-5 v7
Integer to boolean 16 conversion with logic node representation function (ITBGAPC) is used to
transform an integer into a set of 16 boolean signals. ITBGAPC function can receive an integer
from a station computer – for example, over IEC 61850–8–1. This function is very useful when
the user wants to generate logical commands (for selector switches or voltage controllers) by
inputting an integer number. ITBGAPC function has a logical node mapping in IEC 61850.
The Integer to Boolean 16 conversion with logic node representation function (ITBGAPC) will
transfer an integer with a value between 0 to 65535 communicated via IEC 61850 and
connected to the ITBGAPC function block to a combination of activated outputs OUTx where
1≤x≤16.
The values of the different OUTx are according to the Table
.
If the BLOCK input is activated, it freezes the logical outputs at the last value.
Table 5:
Output signals
Name of OUTx
Type
Description
Value when
activated
Value when
deactivated
OUT1
BOOLEAN
Output 1
1
0
OUT2
BOOLEAN
Output 2
2
0
OUT3
BOOLEAN
Output 3
4
0
OUT4
BOOLEAN
Output 4
8
0
OUT5
BOOLEAN
Output 5
16
0
OUT6
BOOLEAN
Output 6
32
0
OUT7
BOOLEAN
Output 7
64
0
OUT8
BOOLEAN
Output 8
128
0
OUT9
BOOLEAN
Output 9
256
0
OUT10
BOOLEAN
Output 10
512
0
OUT11
BOOLEAN
Output 11
1024
0
OUT12
BOOLEAN
Output 12
2048
0
OUT13
BOOLEAN
Output 13
4096
0
OUT14
BOOLEAN
Output 14
8192
0
OUT15
BOOLEAN
Output 15
16384
0
OUT16
BOOLEAN
Output 16
32768
0
The sum of the numbers in column “Value when activated” when all OUTx (1≤x≤16) are active
equals 65535. This is the highest integer that can be converted by the ITBGAPC function block.
4.12
Elapsed time integrator with limit transgression and
overflow supervision TEIGAPC
4.12.1
Identification
GUID-1913E066-37D1-4689-9178-5B3C8B029815 v3
Function Description
IEC 61850
identificatio
n
IEC 60617
identificatio
n
ANSI/IEEE C37.2 device
number
Elapsed time integrator
TEIGAPC
-
-
Section 4
1MRK 511 445-UEN B
Logic
38
Switchgear control unit SAM600-IO
Application manual