
In compensated networks, where distributed compensation coils are
also used to compensate earth-fault current, setting
Operating quantity
should be set to "Resistive". This enables secure and dependable
directional determination also in case of local overcompensation where
the earth-fault current produced by the healthy feeder can become
inductive.
When
Operating quantity is set to "Amplitude", the set minimum operate current
threshold (setting
Min operate current) is compared to the amplitude of
I
o stab
1
in
the whole defined operate sector (see
). This selection can be used in
unearthed networks.
+90 deg.
-90 deg.
+45 deg.
Tilt angle
0 deg.
Figure 325: Operating quantity = "Amplitude" and Directional mode = "Forward"
If the “Adaptive” or “Resistive” operating quantity is selected, the setting
Min
operate current should be set to value:
pu
p IRtot
[
]
<
⋅
(Equation 99)
[pu]
Min operate current
IRtot
Total resistive earth-fault current of the network corresponding to the resistive
current of the parallel resistor of the coil and the natural losses of the system
(typically in order of 1...5 % of the total capacitive earth-fault current of the
network).
p
security factor = 0.5…0.7
It must be set to a value which is lower than the total resistive earth-fault current in
order to enable dependable operation.
Estimation of the total resistive earth-fault current of the network including the
parallel resistor of the coil and the network losses can be obtained from the
Protection functions
1MRS759142 F
566
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......