The third harmonic voltages Ū
3H_T
and Ū
3H_N
are the phasor with its real and
imaginary parts. Ū
3H_T
is approximately in the opposite direction to that of the
Ū
3H_N
, however the actual no-fault angle between those two phasors depends on
the type of generator earthing. For example, the angle is about 145 degrees for a
high-resistance-earthed unit generator.
The equation defines the "operate" and "restrain" regions of the protection. The
third harmonic differential protection operates according to the following equation.
U
U
Beta
U
H
T
H
N
H
N
3
3
3
_
_
_
+
≥
×
(Equation 84)
Ū
3H_N
Neutral side third harmonic voltage phasor
Ū
3H_T
Terminal side third harmonic voltage phasor
Beta
Setting to achieve a required degree of security under healthy conditions
|Ū
3H_T
+Ū
3H_N
| Magnitude of the third harmonic differential voltage
Beta
·|Ū
3H_N
|
Magnitude of the third harmonic bias (restrain) voltage
Factor
Beta, which is a setting, can be determined from the condition.
(Equation 85)
K is the security factor, for example K = 1.5.
must be satisfied in the
normal, healthy condition of the protected generator, with a high enough value for
K, so that no unwanted operation of the protection should be expected, regardless
the load on the generator.
To assure a reliable functioning of the protection, it is necessary that the
generator produces third harmonic voltage which is at least 1% of the
generator rated voltage.
As phase-to-phase voltages do not contain a third harmonic component, in
situations where the VTs on the terminal side are connected between phase-to-
phase, the differential protection in
cannot work. In such case, the
Voltage selection setting is set to "No Voltage" and H3EFPSEF operates as a simple
neutral side third harmonic undervoltage protection.
When H3EFPSEF is reduced to function as only a third harmonic neutral
point undervoltage protection, it is necessary to block the function
during start-up and shutdown of generator and also when there is no
sufficient voltage.
Calculating Beta value
The setting
Beta gives the proportion of the third harmonic voltage in the neutral
point of the generator to be used as bias quantity.
Beta must be set so that there
Protection functions
1MRS759142 F
548
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......