
k
is the set value of
Overload factor
,
ρ
is the set value of
Weighting factor
and
t
is the time constant.
The equation θB is used whenever all phase current is below overload limit i.e. 2.5 ∙
I
IFLC
, whereas equation θA is used when any of the phase current exceeds overload
limit.
During overload condition, the function calculated the θB in background, when
overload ends the thermal level is brought linearly from θA to θB, with speed of
1.66% per second. For the motor at standstill i.e. when the current is below the value
0.12 ∙
I
IFLC
, the cooling can be expressed as:
=
02
−
(Equation 47)
θ
02
= initial thermal level when cooling begins
The thermal behavior can be understood from
A
B
% Thermal capacity
100
80
60
Thermal level
For e.g. at Startup
Thermal level
For e.g. at Standstill
Figure 246: Thermal behavior
The required
Overload factor is used to define the highest permissible continuous
load. The recommended value is at minimum 1.05.
In order to accurately calculate the rotor thermal condition, different time constants
are used in the above equations. These time constants are employed based on
different motor running conditions, for example starting, normal or stop, and are
set through the
Time constant start, Time constant normal, and Time constant stop
settings. Only one time constant is valid at a time. Different running conditions are
defined by the comparison of the
I
IFLC
and the phase currents, which can be seen in
Protection functions
1MRS759142 F
426
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......