Voltage control mode
In the Voltage control mode, the Effective start value is calculated based on the
magnitude of input voltages
U_AB
,
U_BC
and
U_CA
. The voltage dependency is
phase sensitive, which means that the magnitude of one input voltage controls the
start value of only the corresponding phase, that is, the magnitude of voltage inputs
U_AB
,
U_BC
and
U_CA
independently control the current start values of phases A, B
and C.
Two voltage control characteristics, voltage step and voltage slope, can be achieved
with the
Voltage high limit and Voltage low limit settings.
The voltage step characteristic is achieved when the
Voltage high limit setting is
equal to the
Voltage low limit setting. The effective start value is calculated based
on the equations.
Voltage level
Effective start value (I> effective)
U <
Voltage high limit
Start value low
U ≥
Voltage high limit
Start value
In this example, U represents the measured input voltage. This voltage step
characteristic is graphically represented in
Figure 222: Effective start value for voltage step characteristic
The voltage slope characteristic is achieved by assigning different values to
Voltage
high limit and Voltage low limit. The effective start value calculation is based on the
equations.
Voltage level
Effective start value (I> effective)
U <
Voltage low limit
Start value low
U ≥
Voltage high limit
Start value
1MRS759142 F
Protection functions
REX640
Technical Manual
371
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......