Parameter name
Enum name
Value
Load shed mode
None
0
Load shed mode
Instantaneous
1
Load shed mode
Voltage base
2
Load shed mode
Time base
3
The active transfer mode that carries out the transfer action is provided by Transfer
shows the calculation for Transfer mode recorded data
parameter and priority order in case multiple modes are active for bus transfer.
Table 1607: Transfer mode output calculation
Priority order
Cause of Transfer
Transfer mode output
1
Fast transfer completed &
Transfer cause > 0
1=Fast transfer
2
FBBM transfer completed &
Transfer cause > 0
2=FBBM
3
1
st
phase coincidence trans-
fer completed & Transfer
cause > 0
3=Phase coincidence
4
Residual voltage transfer
completed & Transfer cause >
0
4=Res Voltage transfer
5
Time delay transfer comple-
ted & Transfer cause > 0
5=Time delay transfer
6
None
0=None
The transfer direction from feeder 1 to feeder 2 or vice – versa is recorded by
Transfer direction recorded data parameter.
The maximum rate of change of busbar voltage, the maximum rate of change of
frequency and frequency difference between stand-by feeder and busbar, busbar
frequency, busbar voltage, phase angle difference between stand-by feeder and
busbar are provided by Max dv/dt, Max df/dt, Bus frequency, Bus voltage, Phase
Diff recorded data parameters respectively at the instance transfer complete is
activated.
9.12.6
Application
The High speed transfer device is utilized where the availability of a safe voltage
supply is important and where a breakdown of the electrical energy supply would
mean an interruption in production and thus lead to costs and/or damages as a
result.
The usual areas of installation include, for example:
1. Auxiliary distributions in power stations, for example
1MRS759142 F
Control functions
REX640
Technical Manual
1787
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......