Measured circuit breaker opening and closing times are shown in the
monitored data with outputs
CB_OPN_T_CB1
,
CB_OPN_T_CB2
,
CB_CLS_T_CB1
and
CB_CLS_T_CB2
.
An alarm is issued in case circuit breaker opening or closing time exceeds the set
limits. Opening time alarm limit is set with setting
CB open alarm time and closing
time alarm limit is set with setting
CB close alarm time.
An alarm is also issued in case closing time between consecutive closings varies
more than set by setting
CB closing time Dif.
Alarm outputs are
AL_OPN_CB1
and
AL_CLS_CB1
for circuit breaker 1 and
AL_OPN_CB2
and
AL_CLS_CB2
for circuit breaker 2.
Circuit breaker closing time measurement, “From Cmd to Pos”
“From Cmd to Pos” mode measures the closing time from binary output activation
till position change has been indicated by auxiliary contacts.
shows an example of CB closing time measurement in “From Cmd to
Pos” mode.
POSOPN_CB2 – AUX BIN
POSCLS_CB2 – AUX BIN
Current in Feeder 2 / CB2
OPEN_CB2 – FB CMD
CLOSE_CB2 – FB CMD
RELAY BINARY OUTPUT
Closing
�m
e
1 2
4
3
Internal Logic + BO ac
�
va
�
on delay
Figure 949: Circuit breaker closing time measurement (“From Cmd to Pos”)
1
HSABTC function activates
CLOSE_CB2
output
2
Relay binary output activates – closing time measurement starts from this
point
3
Circuit breaker main contacts close
4
Close position indicated to relay with auxiliary contacts
Closing time is time from 2 to 4
1MRS759142 F
Control functions
REX640
Technical Manual
1783
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......