9.12.5.1
Voltage monitoring
Voltage monitoring module calculates measurement values necessary in HSABTC
internal operation. Functionally module can be split to submodules presented in
. Each module is explained later below.
U3P1
U3P2
U3P_BB
U_AB_1
U_BC_1
U_CA_1
U_AB_2
U_BC_2
U_CA_2
U_AB_BB
FRQ_MEAS_1
FRQ_MEAS_2
FRQ_MEAS_BB
ANG_DIFF_1
Amplitude
calculation
Frequency
calculation
Angle
calculation
ANG_DIFF_2
F1_U_A_AB
F1_U_B_BC
F1_U_C_CA
F2_U_A_AB
F2_U_B_BC
F2_U_C_CA
BB_U_A_AB
Figure 933: Voltage monitoring module diagram.
Amplitude calculation
Amplitude calculation reports phase-to-phase voltages from busbar (U_AB_BB),
feeder 1 (U_AB_1, U_BC_1, U_CA_1) and feeder 2 (U_AB_2, U_BC_2, U_CA_2).
Frequency calculation
This module calculates the frequencies of feeder 1, feeder 2 and busbar. The
calculated frequencies for feeder 1, feeder 2 and busbar, FRQ_MEAS_1, FRQ_MEAS_2
and FRQ_MEAS_BB respectively, are available as function outputs.
Angle calculation
This module calculates phase angle difference between feeder 1 and busbar
(ANG_DIFF_1), and between feeder 2 and busbar (ANG_DIFF_2). Values are available
in monitored data view.
9.12.5.2
Transfer direction
The module checks the present transfer direction and stores the valid saved transfer
direction from the breaker’s auxiliary contact states. Functionally module can be
split to submodules presented in
. Each module is explained later below.
1MRS759142 F
Control functions
REX640
Technical Manual
1763
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......