accuracy. The recommendation for the CT is a primary current equivalent to the
coil's maximum current and accuracy class 0.5S or better. The
IRES
signal is not
sufficient for the controller as it does not allow manual control of the coil if it is
disconnected from the network.
All voltage and current signals are measured using the value of the filtered
fundamental frequency component (DFT). Hence, the harmonics are always
suppressed.
Status information
The connection status (
COIL_STS
) information from the adjustable arc suppression
coil disconnector or circuit breaker should be wired to the controller. Also, fixed
parallel coil status (
FIXCOIL_STS
) and the parallel resistor status (
RESISTOR_STS
)
should be wired to the controller if they are present in the system. Inactive status
information signal means that the device is not connected and active status
information signal means that the device is connected.
Outputs
The following outputs should be considered in order to ensure correct operation of
the controller if a fixed parallel coil or parallel resistor is installed in the network:
•
FIXCOIL
,
OP_FIXCOIL
and
CL_FIXCOIL
: Status signal and corresponding open
and close command signals, with 100 ms fixed pulse length for controlling the
circuit breaker or disconnector of the fixed parallel coil. These signals are applied
if a fixed parallel coil is installed in the system.
•
RESISTOR
,
OP_RESISTOR
and
CL_RESISTOR
: Status signal and corresponding
open and close command signals, with 100 ms fixed pulse length for controlling
the contactor, circuit breaker or disconnector of the parallel resistor. These
signals are applied if a parallel resistor is installed in the system.
An example configuration of the connections is shown in
. Controller
inputs are indicated with red lines and outputs with green lines. This example shows
a simple, one-controller setup without the parallel resistor of the coil.
Figure 922: Example configuration of the controller connections
Control functions
1MRS759142 F
1732
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......