
OL5ATCC includes the line drop compensation (LDC) functionality, and the load
decrease is possible with a dynamic voltage reduction. Further, OL5ATCC can
manage voltage regulation in case of reverse power flow.
Either definite time characteristic ( DT) or inverse time characteristic ( IDMT) is
selectable for delays between the raising and lowering operations.
The function contains a blocking functionality. It is possible to block the voltage
control operations with an external signal or with the supervision functionality of
the function.
9.10.4
Analog channel configuration
Function block OL5ATCC has four analog group inputs which all must be properly
configured. The table below presents inputs and their purpose.
Table 1569: Analog inputs
Input
Purpose
I3P1
Three-phase currents from transformer secondary side.
U3P1
Three-phase voltages from transformer secondary side.
I3P2
1
Three-phase currents from transformer primary side.
U3P2
1
Three-phase voltages from transformer primary side.
Please refer to Preprocessing function block section in this manual for
possible signal sources.
There are few special conditions which must be noted with configuration. See
.
Table 1570: Special conditions
Condition
Note
U3P1 or U3P2 connected to
real measurements
Function can work with one voltage connected to channel 1
or with two voltages connected to channels 2 and 3 or with
all three voltage channels connected.
Improper analog channel configuration causes validation error in
Application configuration tool. In such a case analog channels and certain
settings are not matching. For troubleshooting, check the given material
in this chapter. Configuration can be written to relay once the mismatch
is corrected.
9.10.5
Operation principle
The function can be enabled and disabled with the
Operation setting. The
corresponding parameter values are "On" and "Off".
The operation of OL5ATCC can be described with a module diagram. All the modules
in the diagram are explained in the next sections.
1
Should be connected to GRPOFF if HV side measurements are not available when “Regulation
mode” is “Forward” or “Bi-dir(calc)”
Control functions
1MRS759142 F
1696
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......