
• The measured difference of the voltages is less than the set value of
Difference
voltage.
• The measured difference of the phase angles is less than the set value of
Difference angle.
• The measured difference in frequency is less than the set value of
Frequency
difference.
• The estimated breaker closing angle is decided to be less than the set value of
Difference angle.
Dead line or bus value
Live line or bus value
Difference angle
U_Bus
U_Line
Difference voltage
f
U_Bus
f
U_Line
Frequency[Hz]
f
= abs(
f
U_Bus
-
f
U_Line
)
Rated frequency
Frequency deviation
=
U_Bus
-
U_Line
Difference frequency
Figure 844: Conditions to be fulfilled when detecting synchronism between systems
When the frequency, phase angle and voltage conditions are fulfilled, the duration
of the synchronism conditions is checked so as to ensure that they are still met
when the condition is determined on the basis of the measured frequency and
phase difference. Depending on the circuit breaker and the closing system, the delay
from the moment the closing signal is given until the circuit breaker finally closes
is about 50...250 ms. The selected
Closing time of CB informs the function how
long the conditions have to persist. The Synchro check function compensates for
the measured slip frequency and the circuit breaker closing delay. The phase angle
advance is calculated continuously with the formula.
Closing angle
= ∠
− ∠
(
)
° +
−
(
)
×
+
(
)
×
°
(
)
U
U
f
f
T
T
Bus
Line
Bus
line
CB
PL
360
(Equation 352)
∠ U
Bus
Measured bus voltage phase angle
∠U
Line
Measured line voltage phase angle
f
Bus
Measured bus frequency
f
line
Measured line frequency
T
CB
Total circuit breaker closing delay, including the delay of the protection relay
output contacts defined with the
Closing time of CB
setting parameter value
T
PL
Output type dependent delay according to
Table 1505: Typical delays for different output types
Output type
Recommended value for T
PL
Semiconductor output (HSO, SPO)
0 ms
Mechanical relay output (POSP, PODP, PO)
6 ms
1MRS759142 F
Control functions
REX640
Technical Manual
1547
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......