Function
Settings
Minimum/maximum
Phase sequence current measurement
(CSMSQI)
Ps Seq A deadband
,
Ng Seq A deadband
,
Zro A deadband
0.04/40
Phase sequence voltage measurement
(VSMSQI)
Ps Seq V deadband
,
Ng Seq V deadband
,
Zro V deadband
0.004/4
Three-phase power and energy measurement
(PEMMXU)
Power deadband
0.01/0.1
Power and energy calculation
The three-phase power is calculated from the selected voltage and current
measurements as described in
. The setting
Measurement mode
determines which voltage and current measurements are used.
It is also possible to use positive-sequence components for calculating the apparent
power, which makes the determination of power insensitive to any asymmetry in
currents or voltages.
Table 1360: Measured apparent power
Measurement mode
setting
values
Power calculation
PhsA, PhsB, PhsC
S
U
I
U
I
U
I
A
A
B
B
C
C
=
⋅
+
⋅
+
⋅
*
*
*
(Equation 339)
Arone
S
U
I
U
I
AB
A
BC
C
=
⋅
−
⋅
*
*
(Equation 340)
Pos Seq
S
U
I
=
⋅
⋅
3
1
1
*
(Equation 341)
PhsAB
S
U
I
I
AB
A
B
=
⋅
−
(
)
*
*
(Equation 342)
PhsBC
S
U
I
I
BC
B
C
=
⋅
−
(
)
*
*
(Equation 343)
PhsCA
S
U
I
I
CA
C
A
=
⋅
−
(
)
*
*
(Equation 344)
Table continues on the next page
1MRS759142 F
Measurement functions
REX640
Technical Manual
1439
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......