3.7.2.2
Test mode
The function has two outputs,
BEH_TST
and
BEH_BLK
, which are activated in test
mode according to
Table 65: Test mode
Test mode
Description
Protection
BEH_BLK
Protection
BEH_TST
Normal mode
Normal operation
FALSE
FALSE
IED blocked
Protection works as
in “Normal mode” but
the ACT configuration
can be used to block
physical outputs to
process. Control func-
tion commands are
blocked.
TRUE
FALSE
IED test
Protection works as
in “Normal mode” but
protection functions
work in parallel with
test parameters.
FALSE
TRUE
IED test and blocked
Protection works as
in “Normal mode”
but protection func-
tions work in par-
allel with the test
parameter. The ACT
configuration can be
used to block physical
outputs to process.
Control function com-
mand is blocked.
TRUE
TRUE
For more information, see the Test mode section in this manual.
3.7.2.3
Frequency adaptivity
The
FRQ_ADP_WARN
output is active when full adaptation to the actual frequency is
not reached or guaranteed. The
FRQ_ADP_FAIL
output is active when no frequency
source has sufficient amplitude and the nominal frequency window size is used
in measurements. The
FRQ_ADP_BU
output is active when the backup adaptivity
frequency source is active.
When switching from the main frequency source to the backup frequency source,
there is an interval of 200 ms where the last known frequency is used to determine
the measurement window size. During this period,
FRQ_ADP_WARN
is activated.
This also happens when no frequency source has sufficient amplitude and the last
frequency is held for 3 s before activating output
FRQ_ADP_FAIL
.
1MRS759142 F
Basic functions
REX640
Technical Manual
133
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......