Taps or spurs in the feeder
If the protected feeder consists of taps or spurs, the measured fault impedance
corresponds to several physical fault locations (For example, A or B in
). The actual fault location must be identified using additional information, for
example, short circuit current indicators placed on tapping points.
Figure 693: Fault on a distribution line with spurs
5.7.5.4
Trigger detection
The fault distance estimate is obtained when SCEFRFLO is triggered. The triggering
method is defined with setting
Calculation Trg mode. The options for selection are
"External" or "Internal", where the default value is "External". The TRIGG_OUT event
indicates the fault distance value recording moment. The fault distance estimate,
Flt distance, together with the time stamp of actual triggering are saved in the
recorded data of SCEFRFLO.
• In case of external triggering, an external trigger signal should be connected
to the
TRIGG_REC
input. The triggering signal is typically a trip signal from
a protective function. At triggering moment the fault distance is stored into
recorded data. It is important that triggering be timed suitably to provide
sufficient time for the distance estimation calculation before tripping of the
feeder circuit breaker.
• In case of internal triggering, the
TRIGG_REC
input is not used for triggering.
Instead, the trigger signal is created internally so that the estimation is started
when Phase selection logic detects a fault and the estimate is triggered when
its value has stabilized sufficiently. This is judged by maximum variation in
fault distance estimate and defined with setting
Distance estimate Va (in the
same unit as the fault distance estimate). When successive estimates during
one fundamental cycle are within “final value ±
Distance estimate Va”, the fault
distance estimate (mean of successive estimates) is recorded. If the stabilization
criterion has not been fulfilled, the fault distance estimate is given right before
the fault ends. Phase selection logic is a non-directional function so internal
triggering should not be used when directionality is required.
Generally, SCEFRFLO requires a minimum of two fundamental cycles of measuring
time after the fault occurrence.
illustrates typical behavior of fault
distance estimate of SCEFRFLO as a function of time.
Protection related functions
1MRS759142 F
1214
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......