Figure 651: Equation
If the system is symmetrical, that is, the system is healthy without any fault
U
U
U
A
B
C
+
+
=
0
Figure 652: Equation
Combining
results in
U
k
U
U
k
A
A
N
+
⋅ −
(
)
=
⋅
+
⋅
(
)
1 2
Figure 653: Equation
U
U
k
k
N
A
=
⋅
−
(
)
+
⋅
(
)
1
1 2
Figure 654: Equation
Considering the neutral VT ratio, per unit voltage referred to the neutral side is
given by
U
U
k
k
U
N
A
N
pr
=
⋅
−
(
)
+
⋅
(
)
1
1 2
_
Figure 655: Equation
For example, if the impedance of the 20 kV system (U
A
= 11.547 kV) capacitance
drops by 5 percent, that is, k = 0.95, the neutral voltage is around 200 V according
to
. If the voltage rating of a neutral VT is 20 kV/100 V, then in per unit
terms refer to neutral side, the neutral voltage is around 0.01 · Un, that is,
Start value
should be set around 0.01.
In addition, assume that residual voltage (terminal side) is measured directly using
an open-delta VT having ratio of
20
3
100
3
100
3
kV
V
V
/
/
. Also, the
Primary voltage
and
Secondary voltage settings under Configuration > Analog inputs > Voltage
(UoB,VT) in a grounded system are set as 11.547 kV and 100 V, respectively. Similarly,
if the VT connected at the neutral point has a ratio of
20
3
100
3
kV
V
/
, the
Primary
voltage and Secondary voltage settings under Configuration > Analog inputs >
Voltage (UoB,VT) must be set as 20 kV and 100 V, respectively.
4.12.5.8
Signals
Protection functions
1MRS759142 F
1154
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......