response of the High pass filter and all the harmonic Band stop filters are shown in
Figure 640: Magnitude response of High pass and all the harmonic Band stop filters
Similarly resonance current is calculated in the same way for phase B and phase
C. Resonance currents
I_RESO_A
,
I_RESO_B
and
I_RESO_C
are available in the
monitored data view.
The maximum of the three calculated resonance currents is further considered for
calculation.
I
RESONANCE
Max I
RESO
A I
RESO
B I
RESO
C
_
( _
_
_
_
_
_
=
,
,
)
(Equation 290)
If a capacitor bank is used only for reactive power compensation and
there is no series reactor in a filter branch, the resonance protection is
very important. In this case, the setting
Tuning harmonic Num should be
set to 1 because the capacitor branch is not tuned for a special frequency
as in tuned filter applications. Even though
Tuning harmonic Num is set
to 1, the fundamental component is subtracted only once from I
RMS
.
Level detector 1
The maximum calculated resonance current is compared to the set
Alarm start
value. If the calculated
I_RESONANCE
exceeds the set
Alarm start value, the module
sends the enabling signal to the Timer 1 module.
Level detector 2
The maximum calculated resonance current is compared to the set
Start value. If
the calculated
I_RESONANCE
exceeds the set
Start value, this module sends the
enabling signal to the Timer 2 module.
Protection functions
1MRS759142 F
1144
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......