Impedance calculation
This module receives positive sequence voltage (U
1
) and negative sequence voltage
(U
2
) which are calculated from fundamental frequency three phase voltages.
Also positive sequence current (I
1
) and negative sequence current (I
2
) which are
respectively calculated from fundamental frequency three phase currents.
Once activated the negative sequence impedance (Z
2
) is calculated from the
negative sequence current, the negative sequence voltage and Relay characteristic
angle (RCA) using the below equation.
(Equation 278)
The RCA in the above equation can be obtained from
Characteristic angle setting.
The Z
2
value in primary ohms is available as Z2_VALUE in monitored data.
Table 972: Direction value for monitored data view
Criterion for direction information
The value for DIRECTION
Default (low level blocking active)
0 = unknown
Z
2
> 0
1 = forward
Z
2
< 0
2 = backward
Fault direction detector
This module checks if the value of Z
2
meets the operation criteria. Detection to only
forward direction can be achieved by setting the
Direction mode to “Forward”. Thus,
forward fault is detected if the value of Z
2
is higher than the
Ng Seq impedance Fw
setting. Respectively operation to only reverse direction can be activated by setting
Direction mode is set to “Reverse”. Reverse fault is detected if the value of Z
2
is
below the setting
Ng Seq impedance Rv setting. In case Direction mode is set to
“Non-directional”, operation is allowed if condition for forward or reverse direction
is fulfilled.
The
Ng Seq impedance Fw setting and Ng Seq impedance Rv settings are
set in primary ohms.
FAULT_DIR gives the direction information during fault, if operation criteria is
satisfied. that is, when the
START
output is active. The fault direction (FAULT_DIR) is
available in monitored data and as function block output. FAULT_DIR values are the
same as for
DIRECTION
output given in the
. The FAULT_DIR is set to value
0 = unknown after the
START
output is deactivated.
illustrates the directional operating characteristics on negative sequence
impedance level as shown in the vertical line.
Protection functions
1MRS759142 F
1040
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......