Table 970: Analog Inputs
Input
Description
I3P
Three phase currents
U3P
Three phase voltages
Table 971: Special conditions
Condition
Description
U3P connected real measurements
The function requires that at least two volt-
age channels are connected
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings.
4.7.5.5
Operation principle
The
Operation setting is used to enable or disable the function. When selected "On"
the function is enabled and respectively "Off" means function is disabled.
The operation of DNZPDIS can be described by using a module diagram ( see
below). All the modules in the diagram are explained in the next sections.
BLOCK
OPERATE
Blocking
logic
START
Impedance
calculation
Low Level
blocking
Fault
direction
detector
FAULT_DIR
DIRECTION
U3P
I3P
U
2
I
2
I
1
t
Timer
Figure 578: Functional module diagram
Low level blocking
This module receives positive sequence current (I
1
) and negative sequence current
(I
2
). Both are calculated from fundamental frequency three phase currents.
Low level blocking is used to block the Impedance calculation if negative sequence
current does not satisfy minimum level criteria. If negative sequence current
exceeds setting
Min Ng Seq current Fw value, impedance calculation is allowed in
forward direction. Alternatively, if negative sequence current is exceeds setting
Min
Ng Seq current Rv value, impedance calculation is allowed in reverse direction.
The negative sequence current to positive sequence current ratio (I
2
/I
1
) should also
exceed the setting
Restrain factor to enable impedance calculation.
1MRS759142 F
Protection functions
REX640
Technical Manual
1039
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......