Mho circle entirely and the setting
Zone 3 enable is also set to “Yes”. Increment of
the slip counter triggers also the Reset timer. All of the zone slip counters reset after
the set
Reset time has elapsed and the impedance does not cross into the outer
blinder again, or on activation of the
OPERATE
output.
When the “Way out” or "Adaptive" option is selected, the breaker open time, if
known, can be incorporated to optimize breaker trip time when a way out trip
command is issued. The ideal time for the breaker to interrupt current is when the
swing angle approaches zero. If the swing angle is δ
0
when the impedance exits the
outer blinder, the dynamic Trip delay, T
od
, can be set as shown in
.
T
f
T
BrkropenTm
f
od
slip
co
slip
=
− ⋅
⋅
+
⋅
1 2
2
(
)
(Equation 273)
T
od
Dynamic Trip delay
T
co
The time for the impedance to travel from the center impedance line (where
the swing angle is π radians) to the outer blinder on the opposite side from
which it entered.
BrkopenTm Set
Breaker open time
f
slip
Slip frequency
The
Breaker open time setting should include the time from when the relay issues
a trip command to the time when the breaker receives the command. The function
uses the
Breaker open time setting to determine the trip delay time if it is not set
to “0”. If the
Breaker open time is set to “0”, the function does not dynamically
calculate a trip delay but uses the fixed
Operate delay time before activating the
OPERATE
output.
The slip frequency is calculated using
.
f
T
slip
i
oi
=
−
⋅
⋅
δ
δ
π
0
2
(Equation 274)
f
slip
Slip frequency
T
oi
The time for the impedance to pass from the outer to the inner blinder.
δ
0
Swing angle at the outer blinder
δ
I
Swing angle at the inner blinder
The swing angles, δ
0
and δ
I
, are estimated from the measured impedance when
crossing the blinders. It is the difference in these quantities that is important for
determining the slip frequency.
If the “Adaptive” option is selected, after detecting an OSB condition, the function
further examines the slip frequency f
slip
,
V dip time setting, and swing angle at the
outer blinder (δ
0
) to determine if the operate is asserted on the way in or on the
way out.
OPERATE
is activated on the way in, entering the mho circle from an inner
blinder, if the relationship in
Protection functions
1MRS759142 F
1010
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......