Figure 15:
View I/O page
4.5.5
Testing binary outputs
BIO-Tester provides LED indication next to each binary output. When a binary output
is activated from the LHMI, its LED lights up. This way, the status of activated binary
outputs can be monitored on BIO-Tester.
If the contact type of the binary output is “Normally Open / Normally Close” (NO/
NC), its LED is yellow to indicate “Normal” mode and green when they are activated.
If the binary output type is “Normally Open” (NO), activation of such a contact is
indicated by a green LED.
Table 7:
LED status of outputs
LED
Color
Decsription
Off
-
Yellow
Normal mode (NO/NC)
Green
Activated (NO)
Activated (NO/NC)
Internal fault signal output (change-over/form C) IRF is a single contact included in
the power supply module of the protection relay. This IRF NO / NC type contact is
shown green when it is in “Normal” mode and when it is activated, the LED is shown
as red.