4.2.4.1
Example
SEMOD55055-47 v3
Consider a VT with the following data:
132kV 120V
3
3
EQUATION1937 V1 EN-US
(Equation 1)
The following setting should be used:
VTprim=132
(value in kV)
VTsec=120
(value in
V)
4.2.4.2
Examples how to connect, configure and set VT inputs for most
commonly used VT connections
SEMOD55055-60 v6
Figure
defines the marking of voltage transformer terminals commonly used around
the world.
A
(H1)
B
(H2)
b
(X2)
a
(X1)
A
(H1)
N
(H2)
n
(X2)
a
(X1)
b)
c)
A
(H1)
N
(H2)
dn
(X2)
da
(X1)
d)
V
Pri
+
+
V
Sec
a)
ANSI11000175_1_en.vsd
ANSI11000175 V1 EN-US
Figure 20:
Commonly used markings of VT terminals
Where:
a)
is the symbol and terminal marking used in this document. Terminals marked with a square
indicate the primary and secondary winding terminals with the same (positive) polarity
b)
is the equivalent symbol and terminal marking used by IEC (ANSI) standard for phase-to-
ground connected VTs
c)
is the equivalent symbol and terminal marking used by IEC (ANSI) standard for open delta
connected VTs
d)
is the equivalent symbol and terminal marking used by IEC (ANSI) standard for phase-to-phase
connected VTs
It shall be noted that depending on national standard and utility practices the rated
secondary voltage of a VT has typically one of the following values:
1MRK 504 163-UUS A
Section 4
Analog inputs
Transformer protection RET670 2.2 ANSI
87
Application manual
Содержание RELION RET670
Страница 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 64: ...58 ...
Страница 74: ...68 ...
Страница 104: ...98 ...
Страница 194: ...188 ...
Страница 518: ...512 ...
Страница 618: ...612 ...
Страница 648: ...642 ...
Страница 666: ...660 ...
Страница 672: ...666 ...
Страница 682: ...676 ...
Страница 844: ...838 ...
Страница 868: ...862 ...
Страница 956: ...950 ...
Страница 964: ...958 ...
Страница 1004: ...998 ...
Страница 1014: ...1008 ...
Страница 1015: ...1009 ...