protection are measured on the protected generator output terminals side (HV-
side), then invertion is necessary (
InvertCTCurr
=
Enabled
), provided that the
CT’s actual direction complies with ABB recommendations, as shown in Table
.
8.18
Automatic switch onto fault logic ZCVPSOF
SEMOD153633-1 v3
8.18.1
Identification
SEMOD155890-2 v4
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Automatic switch onto fault logic
ZCVPSOF
-
-
8.18.2
Application
M13830-3 v6
Automatic switch onto fault logic, voltage- and current-based function ZCVPSOF is a
complementary function to impedance measuring functions, but may use the
information from such functions.
With ZCVPSOF, a fast trip is achieved for a fault on the whole line when the line is
being energized. The ZCVPSOF tripping is generally non-directional to secure a trip at
fault situations where directional information cannot be established, for example, due
to lack of polarizing voltage when a line potential transformer is used.
Automatic activation based on dead-line detection can only be used when the voltage
transformer is situated on the line side of a circuit breaker.
When line side voltage transformers are used, the use of the nondirectional distance
zones secures switch onto fault tripping for close-in three-phase short circuits. The use
of the nondirectional distance zones also gives a fast fault clearance when energizing a
bus from the line with a short circuit fault on the bus.
Other protection functions like time-delayed phase and zero-sequence overcurrent
function can be connected to ZCVPSOF to increase the dependability in the scheme.
When the voltage transformers are situated on the bus side, the automatic switch onto
fault detection based on dead-line detection is not possible. In such cases the deadline
detection is bypassed using the breaker closing status and the switch onto fault logic is
activated.
Section 8
1MRK 504 163-UUS A
Impedance protection
488
Transformer protection RET670 2.2 ANSI
Application manual
Содержание RELION RET670
Страница 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 64: ...58 ...
Страница 74: ...68 ...
Страница 104: ...98 ...
Страница 194: ...188 ...
Страница 518: ...512 ...
Страница 618: ...612 ...
Страница 648: ...642 ...
Страница 666: ...660 ...
Страница 672: ...666 ...
Страница 682: ...676 ...
Страница 844: ...838 ...
Страница 868: ...862 ...
Страница 956: ...950 ...
Страница 964: ...958 ...
Страница 1004: ...998 ...
Страница 1014: ...1008 ...
Страница 1015: ...1009 ...