![ABB RELION RER670 Скачать руководство пользователя страница 224](http://html.mh-extra.com/html/abb/relion-rer670/relion-rer670_applications-manual_4708224.webp)
12.1.3.1
Single circuit breaker with single busbar
M12324-3 v12
WA1_MCB
LINE
WA1
QB1
QA1
IEC16000123-1-en.vsdx
LINE_VT
LINE_MCB
WA1_MCB
SESRSYN
U2PBB*
U2PLN*
UBOK
UBFF
ULOK
ULFF
WA1_VT
WA1_VT
LINE_VT
LINE_MCB
WA1_MCB
IEC16000123 V1 EN-US
Figure 69:
Connection of SESRSYN function block in a single busbar
arrangement
illustrates connection principles for a single busbar. For the SESRSYN
function there is one voltage transformer on each side of the circuit breaker. The
voltage transformer circuit connections are straightforward; no special voltage
selection is necessary.
The voltage from busbar VT is connected to U2PBB and the voltage from the line
VT is connected to U2PLN. The conditions of the VT fuses shall also be connected
as shown above.
12.1.4
Setting guidelines
M12550-3 v14
The setting parameters for the Synchronizing, synchrocheck and energizing check
function SESRSYN are set via the local HMI (LHMI) or PCM600.
This setting guidelines describes the settings of the SESRSYN function via the
LHMI.
Common base IED value for primary voltage ( UBase ) is set in a Global base
value function, GBASVAL, found under
Main menu//Configuration/Power
system/GlobalBaseValue/GBASVAL_X/UBase
. The SESRSYN function has one
setting for the bus reference voltage (
GblBaseSelBus
) and one setting for the line
reference voltage (
GblBaseSelLine
) which independently of each other can be set
to select one of the twelve GBASVAL functions used for reference of base values
(e.g. when a power transformer is installed in-between two VTs used for the
function). This means that the reference voltage of bus and line can be set to
different values. The settings for the SESRSYN function are found under
Main
menu/Settings/IED Settings/Control/Synchronizing(25,SC/VC)/
SESRSYN(25,SC/VC):X
has been divided into four different setting groups:
General, Synchronizing, Synchrocheck and Energizingcheck.
Section 12
1MRK 506 375-UEN A
Control
218
Railway application RER670 2.2 IEC
Application manual
Содержание RELION RER670
Страница 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Страница 2: ......
Страница 22: ...16 ...
Страница 48: ...42 ...
Страница 70: ...64 ...
Страница 80: ...74 ...
Страница 100: ...94 ...
Страница 210: ...204 ...
Страница 364: ...358 ...
Страница 384: ...378 ...
Страница 468: ...462 ...
Страница 494: ...488 ...
Страница 504: ...498 ...
Страница 505: ...499 ...