Table 20:
Test settings for synchronizing
Parameter
Setting
Operation
Off
UBase
System voltage level
SelPhaseBus1
UL2
SelPhaseBus2
UL2
SelPhaseLine1
UL2
SelPhaseLine2
UL2
PhaseShift
0 degrees
URatio
1.00
CBConfig
SingleBus
AutoEnerg
Off
ManEnerg
Off
ManEnergDBDL
Off
UHighBusEnerg
80% UBase
UHighineEnerg
80% UBase
ULowBusEnerg
30% UBase
ULowLineEnerg
30% UBase
UMaxEnerg
125% UBase
OperationSynch
On
UHighBusSynch
70% UBase
UHighLineSynch
70% UBase
UDiffSynch
15% UBase
FreqDiffMin
0.01 Hz
FreqDiffMax
0.22 Hz
tMaxSynch
600 sec
OperationSC
On
PhaseDiffM
35 degrees
PhaseDiffA
35 degrees
FreqDiffM
0.01 Hz
FreqDiffA
0.01 Hz
UDiff
15% UBase
tAutoEnerg
0.1 s
tManEnerg
0.1 s
ShortPulse
Off
tClosePulse
0.20 s