LDCM not running the application image
<slot number> is running the factory image instead
of the application image. The factory image is older
and does not contain the latest updates and fixes.
Please reboot the IED. If the problem persists update
the LDCM firmware or replace the board.
LDCM version is not accepted
<device name> firmware version <version string> is
not accepted. The minimum accepted version is
<version string>.
Please update the LDCM firmware or replace the
board.
OEM not running the application image
OEM in slot <slot number> is running the factory
image instead of the application image. The factory
image is older and does not contain the latest
updates and fixes.
Please reboot the IED. If the problem persists, update
the OEM firmware or replace the board.
SFP unplugged from the slot
SFP has been unplugged from the slot
Please check the connection.
Corresponding hardware(s) is set to fail.
SFP replaced with other type
Configured and the detected SFP(s) are different.
Corresponding hardware(s) is set to fail.
Please restart IED and consider Reconfigure HW
modules to get updated hardware list.
Non ABB vendor SFP detected
Non ABB vendor SFP detected.
Corresponding hardware(s) is set to fail. Please use
ABB approved SFP’s.
15.2.4
Hardware re-configuration
GUID-334C5D8B-F383-4CDE-9850-659ED6B405DC v1
When adding, removing or moving a hardware modules in an IED ( for example, I/O modules,
communication modules or time synchronization modules) a set of procedures must be
followed.
Adding a new module in to an IED
Procedure:
1.
Switch the IED off and insert the new module.
2.
Switch the IED on, wait for it to start, and then perform a HW reconfig.
3.
Perform a license update in PCM600.
The new module is now available in PCM600 and is ready to be configured.
Removing a module from an IED
Procedure:
1.
Remove all existing configuration for the module in PCM, and write that configuration to
the IED.
2.
Switch the IED off and remove the HW module.
3.
Switch the IED on, wait for it to start, and then perform a HW reconfig.
4. Perform a license update in PCM 600.
Section 15
1MRK 502 067-UEN B
Troubleshooting
244
Commissioning manual