REG615
Std. conf.
ANSI
IEC
25
27RT
32Q, 27
32R/32O
47O-/59
47U+/27
50L/50NL
60
78V
81
SYNC
U<RT
Q>
→
, 3U<
P>/Q>
U2>/3U>
U1</3U<
ARC
FUSEF
VS
f</f>, df/dt
A
U
12
3U
3I
Io
Common point of coupling
distributed power generation
into the utility network
G
GUID-B99D5D42-A515-43E9-8F1C-74131A760E33 V1 EN
Figure 5.
Application example of combined heat and power/hydro power plant as distributed power generation coupled into the utility network
Standard configurations C and D are intended to be used in
synchronous power generator application where the protection
coverage is a generator, field excitation system and primary
mover. A typical application example is parallel connected
diesel or gas generators with a common step-up transformer
but it can also be a generator in block connection with a
transformer. In medium-size power generator applications
independent and redundant protection system can be a
requirement or the protection system as a whole may require
more than one protection relay in one set-up. Various
recognized earthing principles exist and typically earthing
selection depends on the complete system requirements where
the generator is located. The earth-fault protection depends
mainly on the used earthing principle.
Generator and Interconnection Protection
1MRS758279 B
REG615
Product version: 5.0 FP1
ABB
11