3.12
Type conversion function blocks
3.12.1
QTY_GOOD function block
3.12.1.1
Functionality
The QTY_GOOD function block evaluates the quality bits of the input signal and passes
it as a Boolean signal for the application.
The IN input can be connected to any logic application signal (logic function output,
binary input, application function output or received GOOSE signal). Due to application
logic quality bit propagation, each (simple and even combined) signal has quality which
can be evaluated.
The
OUT
output indicates quality good of the input signal. Input signals that have no
quality bits set or only test bit is set, will indicate quality good status.
3.12.1.2
Signals
Table 46:
QTY_GOOD Input signals
Name
Type
Default
Description
IN
Any
0
Input signal
Table 47:
QTY_GOOD Output signals
Name
Type
Description
OUT
BOOLEAN
Output signal
3.12.2
QTY_BAD function block
3.12.2.1
Functionality
The QTY_BAD function block evaluates the quality bits of the input signal and passes it
as a Boolean signal for the application.
The IN input can be connected to any logic application signal (logic function output,
binary input, application function output or received GOOSE signal). Due to application
logic quality bit propagation, each (simple and even combined) signal has quality which
can be evaluated.
Section 3
1MRS240050-IB C
Basic functions
86
REF615R
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...