Figure 247:
Initiation after elapsed discrimination time - new shot begins
9.2.4.5
Sequence controller
When the
LOCKED
output is active, the AR function is in lockout. This means that new
sequences cannot be initialized, because AR is insensitive to initiation commands. It can
be released from the lockout state in the following ways.
•
The function is reset through communication with the
RsRec
parameter.
•
The lockout is automatically reset after the reclaim time, if the
Auto lockout reset
setting is in use.
If the
Auto lockout reset
setting is not in use, the lockout can be released
only with the
RsRec
parameter.
The AR function can go to lockout for many reasons.
•
The
INHIBIT_RECL
input is active.
•
All shots have been executed and a new initiation is made (final trip).
•
The time set with the
Auto wait time
parameter expires and the automatic sequence
initiation is not allowed because of a synchronization failure.
•
The time set with the
Wait close time
parameter expires, that is, the circuit breaker
does not close or the automatic sequence initiation is not allowed due to a closing
failure of the circuit breaker.
•
A new shot is initiated during the discrimination time.
•
The time set with the
Max wait time
parameter expires, that is, the master unit does
not release the slave unit.
Section 9
1MRS240050-IB C
Control functions
472
REF615R
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...