4.5.1.9
Technical data
Table 241:
49F Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured
current: f
n
±2 Hz
Current measurement: ±1.5% of the set value or
±0.002 × I
n
(at currents in the range of 0.01...4.00 ×
I
n
)
Trip time accuracy
1)
±2.0% of the theoretical value or ±0.50 s
1) Overload current > 1.2 × Trip level temperature
4.6
Differential protection
4.6.1
Numerical stabilized low impedance restricted earth-fault
protection 87LOZREF
4.6.1.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Numerical stabilized low impedance
restricted earth-fault protection
LREFPNDF
dIoLo>
87LOZREF
4.6.1.2
Function block
GUID-136BBBB5-17AB-41B1-81B9-F89CC3E05227 V2 EN
Figure 143:
Function block
4.6.1.3
Functionality
Numerical stabilized low impedance restricted earth-fault protection function
87LOZREF for a two winding transformer is based on the numerically stabilized
differential current principle. No external stabilizing resistor or non-linear resistor are
required.
1MRS240050-IB C
Section 4
Protection functions
REF615R
301
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...