1MRS240173-IB B
Section 5
4x Registers
REF615R
27
DPU2000R Modbus Point List Mitigation Manual
Section 5
4x Registers
5.1
Function Code 3 (Read holding register)
5.1.1
User programmable register block (UDR)
Table 9:
Mitigations of Modbus user defined registers (UDR)
5.1.1.1
Example of remapping a discrete signal to a UDR
Figure 1:
Snapshot of CMT in UDR view
In REF615R, user can reassign the signal to its new bit address using CMT UDR tool. As
Figure 1 shows, user can highlight the signal of "51P (3I>): PHLPTOC1: 1 Trip 51P Trip"
from the left pane, then expand the "Empty Register" from the right pane. In this example,
DPU2000R
REF615R
Number of user defined registers
32
127
Register's starting address
40001
40001
Register's ending address
40032
40127
Configuration method
6x area registers
PCM600 CMT tool
In REF615R, only the signals having IEC61850 paths can be re-assigned
to the user defined registers.