19.2
Redundant communication
19.2.1
Identification
GUID-B7AE0374-0336-42B8-90AF-3AE1C79A4116 v1
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
IEC 62439-3 Parallel redundancy
protocol
PRP
-
-
IEC 62439-3 High-availability seamless
redundancy
HSR
-
-
Access point diagnostic for redundant
Ethernet ports
RCHLCCH
-
-
19.2.2
Application
GUID-172BA5D7-6532-4B0D-8C1D-2E02F70B4FCB v1
Dynamic access point diagnostic (RCHLCCH) is used to supervise and assure
redundant Ethernet communication over two channels. This will secure data transfer
even though one communication channel might not be available for some reason
Parallel Redundancy Protocol (PRP) and High-availability Seamless Redundancy
(HSR) provides redundant communication over station bus running the available
communication protocols. The redundant communication uses two Ethernet ports.
1MRK 511 401-UUS A
Section 19
Ethernet-based communication
Bay control REC670 2.2 ANSI
571
Application manual
Содержание Relion REC670
Страница 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 26: ...20 ...
Страница 42: ...36 ...
Страница 96: ...90 ...
Страница 274: ...268 ...
Страница 292: ...286 ...
Страница 298: ...292 ...
Страница 308: ...302 ...
Страница 470: ...464 ...
Страница 514: ...508 ...
Страница 608: ...602 ...
Страница 646: ...640 ...
Страница 656: ...650 ...
Страница 657: ...651 ...