I3PW1CT1
I3PW2CT1
I3P
REFPDIF (87N)
ANSI11000083_1_en.vsd
ANSI11000083 V1 EN-US
Figure 204:
REFPDIF (87N) function inputs for autotransformer application
For normal transformers only one winding and the neutral point is available. This
means that only two inputs are used. Since all group connections are mandatory to be
connected, the third input needs to be connected to something, which is the GRP_OFF
signal in FXDSIGN function block.
I3PW1CT1
I3PW2CT1
I3P
REFPDIF (87N)
ANSI11000084_1_en.vsd
GRP_OFF
FXDSIGN
ANSI11000084 V1 EN-US
Figure 205:
REFPDIF (87N) function inputs for normal transformer application
16.8
Boolean 16 to Integer conversion B16I
SEMOD175715-1 v1
16.8.1
Identification
SEMOD175721-2 v2
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Boolean 16 to integer conversion
B16I
-
-
1MRK 511 401-UUS A
Section 16
Logic
Bay control REC670 2.2 ANSI
497
Application manual
Содержание Relion REC670