The function shall not operate for any of the calculated currents to the protection. The
minimum theoretical current setting (Imin) will be:
Im
,
fA
fB
in
MAX I
I
EQUATION284 V2 EN-US
(Equation 33)
A safety margin of 5% for the maximum static inaccuracy and a safety margin of 5%
for maximum possible transient overreach have to be introduced. An additional 20% is
suggested due to inaccuracy of instrument transformers under transient conditions and
inaccuracy in the system data.
The minimum primary current setting (Is) is:
I
s
= 1.3 ×
I
min
EQUATION285 V3 EN-US
(Equation 34)
In case of parallel lines with zero sequence mutual coupling a fault on the parallel line,
as shown in Figure
, should be calculated.
~
~
Z
A
Z
B
Z
L1
A
B
I
M
Fault
IED
Z
L2
M
C
Line 1
Line 2
ANSI09000025_2_en.vsd
ANSI09000025 V2 EN-US
Figure 66:
Two parallel lines. Influence from parallel line to the through fault
current: I
M
The minimum theoretical current setting (Imin) will in this case be:
I m in
M A X I
fA
I
fB
I
M
,
,
(
)
³
EQUATION287 V1 EN-US
(Equation 35)
Where:
I
fA
and I
fB
have been described for the single line case.
1MRK 511 401-UUS A
Section 8
Current protection
Bay control REC670 2.2 ANSI
167
Application manual
Содержание Relion REC670
Страница 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 26: ...20 ...
Страница 42: ...36 ...
Страница 96: ...90 ...
Страница 274: ...268 ...
Страница 292: ...286 ...
Страница 298: ...292 ...
Страница 308: ...302 ...
Страница 470: ...464 ...
Страница 514: ...508 ...
Страница 608: ...602 ...
Страница 646: ...640 ...
Страница 656: ...650 ...
Страница 657: ...651 ...