IEC140000128-2-en.vsd
IEC140000128 V2 EN-US
Figure 42:
An example of wrong connection of SMAI and PHASORREPORT
blocks in ACT
Rule 3:
This rule is only related to the connection of 3PHSUM block to the PHASORREPORT
block. If 3PHSUM block is configured to use external DFT reference (from SMAI
reference block), it shall only be connected to the same PHASORREPORT block
instance as the one the SMAI reference block is connected to. In other words, both the
SMAI reference block and 3PHSUM block (3PHSUM block with external DFT
reference) shall be connected to the same instance of PHASORREPORT block
(PHASOR1-32 of Instance number 1 or 2).
shows an example of correct connection of 3PHSUM and
PHASORREPORT blocks in ACT where SMAI3 is configured as the reference block
for DFT reference external out (DFTRefExtOut) and 3PHSUM uses external DFT
reference (from SMAI3). Figures
show the corresponding setting
parameters.
Section 6
1MRK 511 401-UUS A
Wide area measurement system
118
Bay control REC670 2.2 ANSI
Application manual