5.4.4.5
Recorded data
All the information required for a later fault analysis is recorded to SCEFRFLO
recorded data. In the protection relay, recorded data is found in Monitoring >
Recorded data > Other protection > SCEFRFLO.
The function has also monitored data values which are used for the read-out of
continuous calculation values.
shows which of the recorded data values
are available as continuous monitoring values during a fault.
Table 538: Cross reference table for recorded and monitored data values
Recorded data
Monitored data
Flt loop
FAULT_LOOP
Flt distance
FLT_DISTANCE
Flt Dist quality
FLT_DIST_Q
Flt loop resistance
RFLOOP
Flt loop reactance
XFLOOP
Flt phase reactance
XFPHASE
Flt point resistance
RF
Flt to Lod Cur ratio
IFLT_PER_ILD
Equivalent load Dis
S_CALC
XC0F Calc
XC0F_CALC
5.4.4.6
Measurement modes
The full operation of SCEFRFLO requires that all three phase-to-earth voltages are
measured. The voltages can be measured with conventional voltage transformers or
voltage dividers connected between the phase and earth (
VT connection is set to
“Wye”). Another alternative is to measure phase-to-phase voltages (
VT connection
is set to “Delta”) and residual voltage (Uo). Both alternatives are covered by setting
the configuration parameter
Phase voltage Meas to "Accurate".
When the
Phase voltage Meas setting is set to "Ph-to-ph without Uo" and only
phase-to-phase voltages are available (but not Uo), only short-circuit measuring
loops (fault loops “AB Fault”, “BC Fault” or “CA Fault” or “ABC Fault”) can be
measured accurately. In this case, the earth-fault loops (fault loops either “AG Fault”,
“BG Fault” or “CG Fault”) cannot provide correct fault distance estimates and the
triggering of the function in case of earth fault is automatically disabled.
5.4.5
Application
The main objective of the feeder terminals is a fast, selective and reliable operation
in faults inside the protected feeder. In addition, information on the distance to
the fault point is very important for those involved in operation and maintenance.
Reliable information on the fault location greatly decreases the downtime of the
protected feeders and increases the total availability of a power system.
SCEFRFLO provides impedance-based fault location. It is designed for radially
operated distribution systems and is applicable for locating short circuits in all
kinds of distribution networks. Earth faults can be located in effectively earthed
and low resistance/low-reactance earthed networks. Under certain limitations,
1MRS758755 C
Protection related functions
REC615 & RER615
Technical Manual
515