Figure
shows an example how to use BCTZCONN to facilitate the recording of
the zone connection information from one bay, say feeder 01, to a disturbance recorder
in ACT for any six-zone busbar differential protection application.
IEC16000075-1-en.vsdx
IEC16000075 V1 EN-US
Figure 188:
BCTZCONN connection example
13.11
Integer to Boolean 16 conversion with logic node
representation ITBGAPC
SEMOD158419-1 v3
13.11.1
Identification
SEMOD167944-2 v4
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Integer to boolean 16 conversion with
logic node representation
ITBGAPC
-
-
13.11.2
Application
SEMOD158512-5 v7
Integer to boolean 16 conversion with logic node representation function (ITBGAPC)
is used to transform an integer into a set of 16 boolean signals. ITBGAPC function can
receive an integer from a station computer – for example, over IEC 61850–8–1. This
function is very useful when the user wants to generate logical commands (for selector
switches or voltage controllers) by inputting an integer number. ITBGAPC function
has a logical node mapping in IEC 61850.
The Integer to Boolean 16 conversion with logic node representation function
(ITBGAPC) will transfer an integer with a value between 0 to 65535 communicated
via IEC 61850 and connected to the ITBGAPC function block to a combination of
activated outputs OUTx where 1≤x≤16.
1MRK 505 370-UUS A
Section 13
Logic
Busbar protection REB670 2.2 ANSI
419
Application manual
Содержание RELION REB670
Страница 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 24: ...18 ...
Страница 40: ...34 ...
Страница 72: ...66 ...
Страница 102: ...96 ...
Страница 266: ...260 ...
Страница 272: ...266 ...
Страница 290: ...284 ...
Страница 432: ...426 ...
Страница 542: ...536 ...
Страница 552: ...546 ...
Страница 553: ...547 ...