100
2
2
3
IBase
I
PU
I
EQUATION1758-ANSI V4 EN-US
(Equation 83)
where:
I2
is the maximal negative sequence current during normal operating conditions, plus a margin of
10...20%
IBase
is the base current for the function according to the setting
GlobalBaseSel
11.1.3.4
Zero sequence based
M13683-43 v8
The IED setting value
3V0PU
is given in percentage of the base voltage
VBase
. The
setting of
3V0PU
should not be set lower than the value that is calculated according to
100
3
0
3
0
3
VBase
V
PU
V
EQUATION1759-ANSI V4 EN-US
(Equation 84)
where:
3V0
is the maximal zero sequence voltage during normal operation conditions, plus a margin of
10...20%
VBase is the base voltage for the function according to the setting
GlobalBaseSel
The setting of the current limit
3I0PU
is done in percentage of
IBase
. The setting of
pickup must be higher than the normal unbalance current that might exist in the
system. The setting can be calculated according to equation
.
3 0
3 0
100
=
×
I
I PU
IBase
EQUATION2293-ANSI V2 EN-US
(Equation 85)
where:
3I0PU is the maximal zero sequence current during normal operating conditions, plus a margin of
10...20%
IBase
is the base current for the function according to the setting
GlobalBaseSel
Section 11
1MRK 505 370-UUS A
Secondary system supervision
288
Busbar protection REB670 2.2 ANSI
Application manual
Содержание RELION REB670
Страница 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 24: ...18 ...
Страница 40: ...34 ...
Страница 72: ...66 ...
Страница 102: ...96 ...
Страница 266: ...260 ...
Страница 272: ...266 ...
Страница 290: ...284 ...
Страница 432: ...426 ...
Страница 542: ...536 ...
Страница 552: ...546 ...
Страница 553: ...547 ...