A principle overall drawing of how to use REB670 for breaker-and-a-half station
including internal CBF protection for middle breaker is given in Figure
.
en06000149_ansi.vsd
REB 670
OR
BFP
Remote
End
Inter-
Trip
Feeder 1
CTRLZA
CTRLZB
TRIP
CONNZA
CONNZB
Bxxx
I3PB1
BLKTR
TRZONE
TRBAY
Zone A
BBP &
BFP
TRIP
152
BFP
TRIP
252
BBP &
BFP
TRIP
352
BFP
Remote
End
Inter-
Trip
Feeder 2
1½ breaker
Diameter
CTRLZA
CTRLZB
TRIP
CONNZA
CONNZB
Bxxx
I3PB1
BLKTR
TRZONE
TRBAY
BOM
Parameter ZoneSel must
be set to "FixedToZB"
Parameter ZoneSel must
be set to "FixedToZA"
CT Input
TRM
152 Internal BFP
Backup Trip Command
BI2
Zone B
Other
Equipment
Other
Equipment
Other
Equipment
CT Input
CT Input
CTRLZA
CTRLZB
TRIP
CONNZA
CONNZB
Bxxx
I3PB1
BLKTR
TRZONE
TRBAY
A/D
A/D
A/D
Parameter ZoneSel must
be set to "CtrlIncludes"
and CTConnection="Off"
ZERO-
ZERO-
252 Internal BFP
Backup Trip Command
OR
OR
Fe
e
de
r
1
F
e
ed
er
2
352 Internal BFP
Backup Trip Command
BI1
BI3
352
152
252
ANSI06000149 V1 EN-US
Figure 61:
Diameter in breaker-and-a-half station with breaker failure protection
for all three breakers inside REB670
6.1.4.8
Double busbar single breaker arrangement
M6647-3 v5
This type of arrangement is shown in Figure
1MRK 505 370-UUS A
Section 6
Differential protection
Busbar protection REB670 2.2 ANSI
145
Application manual
Содержание RELION REB670
Страница 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 24: ...18 ...
Страница 40: ...34 ...
Страница 72: ...66 ...
Страница 102: ...96 ...
Страница 266: ...260 ...
Страница 272: ...266 ...
Страница 290: ...284 ...
Страница 432: ...426 ...
Страница 542: ...536 ...
Страница 552: ...546 ...
Страница 553: ...547 ...