Table 14:
Typical solutions for single busbar arrangement
Version of REB670 IED
Numbers of feeders per
busbar
Number of REB670 IEDs
required for the scheme
3PH; 2-zones, 4-bays BBP (A20)
4
1
3PH; 2-zones, 8-bays BBP (A31)
8
1
1Ph; 2-zones, 12-bays BBP (B20)
12
3
1Ph; 2-zones, 12-bays BBP (B21)
12
3
1Ph; 2-zones, 24-bays BBP (B31)
24
3
Please note that the above Table
is given for the preconfigured versions of REB670
which do not contain any VT inputs.
6.1.4.3
Single busbar arrangements with sectionalizer
M6642-3 v5
This arrangement is very similar to the single busbar arrangement. The sectionalizer
allows the operator to split the station into two separate buses. However, switching of
the sectionalizing disconnector has to be done without any load. This means that one of
the two busbars has to be de-energized before any opening or closing of the
sectionalizer.
For this case the protection scheme must have two differential zones, which can be
either split to work independently from each other or switched to one overall
differential zone when sectionalizing disconnector is closed. Nevertheless, when
sectionalizer is closed, for internal fault on any of the two buses all feeder circuit
breakers have to be tripped, which causes loss of supply to all loads connected to this
station.
189
ZA
ZB
ANSI11000238-1-en.vsd
152
152
152
152
152
152
152
ANSI11000238 V1 EN-US
Figure 55:
Example of two single busbar sections with bus-sectionalizing
disconnector and eight feeder bays per each busbar section
1MRK 505 370-UUS A
Section 6
Differential protection
Busbar protection REB670 2.2 ANSI
137
Application manual
Содержание RELION REB670
Страница 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 24: ...18 ...
Страница 40: ...34 ...
Страница 72: ...66 ...
Страница 102: ...96 ...
Страница 266: ...260 ...
Страница 272: ...266 ...
Страница 290: ...284 ...
Страница 432: ...426 ...
Страница 542: ...536 ...
Страница 552: ...546 ...
Страница 553: ...547 ...