TripMode
Depending on the setting of the parameter
TripMode:
•
tripping is phase-selective, controlled by the binary input 1PolAR (for 1phTrip), always
three-phase (for 3phTrip)
•
tripping is three-phase after the time
Delay (3) (for 3phTripDel3)
SOTF Mode
Access is gained to the switch-onto-fault logic settings by selecting the parameter
SOTF
Mode. The alternatives presented are whether the switch-onto-fault logic should trip on the
basis of the non-directional underimpedance starters or the overreaching zone.
This logic is enabled either by the undervoltage function delayed by 10 s or 200 ms or the
binary inputs Deadline and Manual close.
Two signaling outputs Start SOTF and Trip SOTF are associated with the switch-onto-fault
logic. Start SOTF is intended for blocking the autoreclosure function and Trip SOTF signals
that tripping was by the switch-onto-fault logic.
SOTF 10 sec
The parameter
SOTF10sec determines whether the undervoltage function and the binary input
Deadline are enabled after 10 s (
on) or 200 ms (off). off indicates switching onto a fault after
fast autoreclosure (Fast AR). Tripping in this case is thus based on the decisions of the
starters alone.
t1EvolFaults
The setting of the parameter
t1EvolFaults determines the time during which the detection of
an evolving fault causes a three-phase trip.
5.1.6.8
Power-swing blocking
GUID-290AFE08-EF8B-49ED-BB97-D443777923B7 v1
Only the parameter
tPSblock for the time during which the power-swing blocking signal is
maintained has to be set in the POWER-SWING BLOCKING sub-menu. The setting range is 0 to
10 s in steps of 0.01. Tripping is enabled again at the latest at the end of this time.
The power-swing blocking function is disabled when
tPSblock is set to zero or a logical 1 is
applied to the binary input Ext Blk PSB.
5.1.6.9
Supplementary information for binary inputs
GUID-1BA1A03D-546C-4875-8F2C-AC972DAE2406 v1
ChgMeasDir
Applying a signal to this input reverses the direction of measurement for the entire distance
protection function (all zones).
Ext Blk Dist
This input blocks the entire distance protection function. Blocking is signaled by Dist blocked
and after 12 s by DelDistBlk. Only the backup overcurrent protection (I O/C) then remains
active.
Ext UZ Blk
This input blocks the underimpedance starters, the neutral voltage starter (U
0
), the
measurement for
Weak and the reverse measurement. The overcurrent starters (OC) remain in
operation.
Section 5
1MRK 505 406-UEN B
Bay protection functions
50
Bay protection functions REB500
Technical manual
© Copyright 2019 ABB. All rights reserved